ZSKN square countercurrent open cooling tower
ZSKN square countercurrent open cooling tower
1. Standard design working conditions: dry bulb temperature 31.5℃, wet bulb temperature 28℃, atmospheric pressure 99400Pa, inlet water temperature 42℃, outlet water temperature 32℃;
2. Use special packing for inclined trapezoidal wave square tower, with excellent thermal performance,
The small ventilation resistance enables this type of cooling tower to achieve the design purpose of compact structure and small footprint;
3. Counter-flow square cooling tower adopts airfoil hollow structure, large diameter, large area, low speed, low dynamic pressure glass fiber reinforced plastic fan blades, the use of this type of cooling tower has the obvious characteristics of energy saving and low noise;
4. The ultra-low noise cooling tower is equipped with noise reduction devices at the air inlet and outlet and rain shower area to effectively reduce the noise of the cooling tower of the same level by 5dB (A);
5. It can be combined in various forms in parallel, which is more suitable for the use of large-volume circulating cooling water systems;
6. The fixed water distribution system is adopted, and the ABS multilayer flow low-pressure sprinkler is selected. The water distribution is uniform, the service life is long, and the water distribution head is low, which is beneficial to save the system water distribution power;
7. Q-235 profiles and FRP profiles can be used for the frame of the counterflow square cooling tower. Although the construction period is slightly longer and the one-time investment is higher, the frame has long service life and low maintenance costs. Users can choose according to the actual situation. ;
8. If the turbidity of circulating water is higher than 50ppm for a long time, or contains impurities such as oil, you need to choose PVC grid filler according to the water quality conditions. The turbidity of the circulating water can be extended to 450ppm.
model | Dimensions | Cooling water m3/h |
fan φ mm |
Motor KW |
weight KG | noise db |
|||||
Model | length L | width W | high H | Tower body H1 | Hair dryer H2 | net weight Dry | Running heavy Wet | ||||
ZSKN-100 | 2460 | 2460 | 4280 | 3240 | 760 | 100 | 1800 | 4 | 1250 | 2320 | 61 |
ZSKN-125 | 2460 | 2460 | 4430 | 3390 | 760 | 125 | 1800 | 4 | 1350 | 2497 | 62 |
ZSKN-150 | 2760 | 2760 | 4720 | 3590 | 820 | 150 | 2100 | 5.5 | 1420 | 2627 | 63 |
ZSKN-175 | 2760 | 2760 | 4720 | 3590 | 820 | 175 | 2100 | 5.5 | 1520 | 2812 | 63.5 |
ZSKN-200 | 3370 | 3370 | 4930 | 3260 | 1000 | 200 | 2400 | 5.5 | 1770 | 3770 | 63.5 |
ZSKN-250 | 3370 | 3370 | 5270 | 3560 | 1000 | 250 | 2400 | 7.5 | 1830 | 3890 | 64 |
ZSKN-300 | 3980 | 3980 | 5160 | 3380 | 1000 | 300 | 3000 | 11 | 2960 | 6590 | 64 |
ZSKN-350 | 3980 | 3980 | 5680 | 3900 | 1000 | 350 | 3000 | 11 | 3150 | 6790 | 64 |
ZSKN-400 | 4895 | 4895 | 5330 | 3260 | 1200 | 400 | 3400 | 15 | 3450 | 7090 | 65 |
ZSKN-450 | 4895 | 4895 | 5480 | 3410 | 1200 | 450 | 3400 | 15 | 4680 | 9760 | 65 |
ZSKN-500 | 4895 | 4895 | 6070 | 3900 | 1200 | 500 | 3400 | 15 | 5420 | 12320 | 66 |
ZSKN-600 | 5810 | 5810 | 5850 | 3650 | 1200 | 600 | 3600 | 18 | 5730 | 12960 | 66 |
ZSKN-700 | 6725 | 6725 | 5650 | 3650 | 1000 | 700 | 4270 | 22 | 6890 | 16310 | 67 |
Note: The parameter changes caused by equipment modification will not be notified separately, and the specific parameters are based on our plan. |
Next